* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -86,13 +86,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 120 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 4 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -85,13 +85,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -80,13 +80,23 @@
#endif
/**
* Thermal Protection parameters for the bed
* are like the above for the hotends.
* WATCH_TEMP_BED_PERIOD and WATCH_TEMP_BED_INCREASE are not imlemented now.
* Thermal Protection parameters for the bed are just as above for hotends.
*/
#if ENABLED(THERMAL_PROTECTION_BED)
#define THERMAL_PROTECTION_BED_PERIOD 20 // Seconds
#define THERMAL_PROTECTION_BED_HYSTERESIS 2 // Degrees Celsius
/**
* Whenever an M140 or M190 increases the target temperature the firmware will wait for the
* WATCH_BED_TEMP_PERIOD to expire, and if the temperature hasn't increased by WATCH_BED_TEMP_INCREASE
* degrees, the machine is halted, requiring a hard reset. This test restarts with any M140/M190,
* but only if the current temperature is far enough below the target for a reliable test.
*
* If you get too many "Heating failed" errors, increase WATCH_BED_TEMP_PERIOD and/or decrease
* WATCH_BED_TEMP_INCREASE. (WATCH_BED_TEMP_INCREASE should not be below 2.)
*/
#define WATCH_BED_TEMP_PERIOD 60 // Seconds
#define WATCH_BED_TEMP_INCREASE 2 // Degrees Celsius
#endif
#if ENABLED(PIDTEMP)

View file

@ -200,11 +200,16 @@ static float analog2temp(int raw, uint8_t e);
static float analog2tempBed(int raw);
static void updateTemperaturesFromRawValues();
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
int watch_target_temp[EXTRUDERS] = { 0 };
millis_t watch_heater_next_ms[EXTRUDERS] = { 0 };
#endif
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
int watch_target_bed_temp = 0;
millis_t watch_bed_next_ms = 0;
#endif
#ifndef SOFT_PWM_SCALE
#define SOFT_PWM_SCALE 0
#endif
@ -717,7 +722,7 @@ void manage_heater() {
if (ct < max(HEATER_0_MINTEMP, 0.01)) min_temp_error(0);
#endif
#if ENABLED(THERMAL_PROTECTION_HOTENDS) || DISABLED(PIDTEMPBED) || HAS_AUTO_FAN
#if (ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0) || (ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0) || DISABLED(PIDTEMPBED) || HAS_AUTO_FAN
millis_t ms = millis();
#endif
@ -734,7 +739,7 @@ void manage_heater() {
soft_pwm[e] = current_temperature[e] > minttemp[e] && current_temperature[e] < maxttemp[e] ? (int)pid_output >> 1 : 0;
// Check if the temperature is failing to increase
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
// Is it time to check this extruder's heater?
if (watch_heater_next_ms[e] && ELAPSED(ms, watch_heater_next_ms[e])) {
@ -751,6 +756,24 @@ void manage_heater() {
#endif // THERMAL_PROTECTION_HOTENDS
// Check if the temperature is failing to increase
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
// Is it time to check the bed?
if (watch_bed_next_ms && ELAPSED(ms, watch_bed_next_ms)) {
// Has it failed to increase enough?
if (degBed() < watch_target_bed_temp) {
// Stop!
_temp_error(-1, PSTR(MSG_T_HEATING_FAILED), PSTR(MSG_HEATING_FAILED_LCD));
}
else {
// Start again if the target is still far off
start_watching_bed();
}
}
#endif // THERMAL_PROTECTION_HOTENDS
#if ENABLED(TEMP_SENSOR_1_AS_REDUNDANT)
if (fabs(current_temperature[0] - redundant_temperature) > MAX_REDUNDANT_TEMP_SENSOR_DIFF) {
_temp_error(0, PSTR(MSG_REDUNDANCY), PSTR(MSG_ERR_REDUNDANT_TEMP));
@ -1160,7 +1183,7 @@ void tp_init() {
#endif //BED_MAXTEMP
}
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
/**
* Start Heating Sanity Check for hotends that are below
* their target temperature by a configurable margin.
@ -1176,6 +1199,22 @@ void tp_init() {
}
#endif
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
/**
* Start Heating Sanity Check for hotends that are below
* their target temperature by a configurable margin.
* This is called when the temperature is set. (M140, M190)
*/
void start_watching_bed() {
if (degBed() < degTargetBed() - (WATCH_BED_TEMP_INCREASE + TEMP_BED_HYSTERESIS + 1)) {
watch_target_bed_temp = degBed() + WATCH_BED_TEMP_INCREASE;
watch_bed_next_ms = millis() + (WATCH_BED_TEMP_PERIOD) * 1000UL;
}
else
watch_bed_next_ms = 0;
}
#endif
#if ENABLED(THERMAL_PROTECTION_HOTENDS) || ENABLED(THERMAL_PROTECTION_BED)
void thermal_runaway_protection(TRState* state, millis_t* timer, float temperature, float target_temperature, int heater_id, int period_seconds, int hysteresis_degc) {

View file

@ -128,17 +128,26 @@ FORCE_INLINE float rawBedTemp() { return current_temperature_bed_raw; }
FORCE_INLINE float degTargetHotend(uint8_t extruder) { return target_temperature[extruder]; }
FORCE_INLINE float degTargetBed() { return target_temperature_bed; }
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
void start_watching_heater(int e = 0);
#endif
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
void start_watching_bed();
#endif
FORCE_INLINE void setTargetHotend(const float& celsius, uint8_t extruder) {
target_temperature[extruder] = celsius;
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
start_watching_heater(extruder);
#endif
}
FORCE_INLINE void setTargetBed(const float& celsius) { target_temperature_bed = celsius; }
FORCE_INLINE void setTargetBed(const float& celsius) {
target_temperature_bed = celsius;
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
start_watching_bed();
#endif
}
FORCE_INLINE bool isHeatingHotend(uint8_t extruder) { return target_temperature[extruder] > current_temperature[extruder]; }
FORCE_INLINE bool isHeatingBed() { return target_temperature_bed > current_temperature_bed; }

View file

@ -603,7 +603,7 @@ void lcd_set_home_offsets() {
/**
* Watch temperature callbacks
*/
#if ENABLED(THERMAL_PROTECTION_HOTENDS)
#if ENABLED(THERMAL_PROTECTION_HOTENDS) && WATCH_TEMP_PERIOD > 0
#if TEMP_SENSOR_0 != 0
void watch_temp_callback_E0() { start_watching_heater(0); }
#endif
@ -631,6 +631,16 @@ void lcd_set_home_offsets() {
#endif // EXTRUDERS > 3
#endif
#if ENABLED(THERMAL_PROTECTION_BED) && WATCH_BED_TEMP_PERIOD > 0
#if TEMP_SENSOR_BED != 0
void watch_temp_callback_bed() { start_watching_bed(); }
#endif
#else
#if TEMP_SENSOR_BED != 0
void watch_temp_callback_bed() {}
#endif
#endif
/**
*
* "Tune" submenu
@ -685,7 +695,7 @@ static void lcd_tune_menu() {
// Bed:
//
#if TEMP_SENSOR_BED != 0
MENU_MULTIPLIER_ITEM_EDIT(int3, MSG_BED, &target_temperature_bed, 0, BED_MAXTEMP - 15);
MENU_MULTIPLIER_ITEM_EDIT_CALLBACK(int3, MSG_BED, &target_temperature_bed, 0, BED_MAXTEMP - 15, watch_temp_callback_bed);
#endif
//